Electronic keying – Rockwell Automation 1784-PM16SE SoftLogix Motion Card Setup and Configuration Manual User Manual
Page 204

Publication 1784-UM003A-EN-P – June 2003
196 Configuring a 1394x-SJTxx-D Digital Servo Drive
The major revision is used to indicate the revision of the interface to the
module. The minor revision is used to indicate the firmware revision.
Electronic Keying
Select one of these keying options for your module during initial module
configuration:
• Exact Match - all of the parameters described below must match or the
inserted module rejects the connection.
• Vendor
• Product Type
• Catalog Number
• Major Revision
• Minor Revision
• Compatible Module
• the Module Types, Catalog Number, and Major Revision must match
• the Minor Revision of the physical module must be equal to or
greater than the one specified in the software
or the inserted module rejects the connection
• Disable Keying – Controller does not employ keying at all.
When you insert a module into a slot in a ControlLogix chassis, RSLogix 5000
compares the following information for the inserted module to that of the
configured slot:
• Vendor
• Product Type
• Catalog Number
• Major Revision
• Minor Revision
ATTENTION
!
Changing the Electronic Keying selection may cause the
connection to the module to be broken and may result in a
loss of data.
Be extremely cautious when using this option; if used
incorrectly, this option can lead to personal injury or death,
property damage or economic loss.