196 Configuring a 1394x-SJTxx-D Digital Servo Drive

The major revision is used to indicate the revision of the interface to the
module. The minor revision is used to indicate the firmware revision.

Electronic Keying

Select one of these keying options for your module during initial module
configuration:

Exact Match - all of the parameters described below must match or the

inserted module rejects the connection.

• Vendor
• Product Type
• Catalog Number
• Major Revision
• Minor Revision

Compatible Module

• the Module Types, Catalog Number, and Major Revision must match
• the Minor Revision of the physical module must be equal to or

greater than the one specified in the software

or the inserted module rejects the connection

Disable Keying – Controller does not employ keying at all.

When you insert a module into a slot in a ControlLogix chassis, RSLogix 5000
compares the following information for the inserted module to that of the
configured slot:

• Vendor
• Product Type
• Catalog Number
• Major Revision
• Minor Revision

ATTENTION

!

Changing the Electronic Keying selection may cause the
connection to the module to be broken and may result in a
loss of data.

Be extremely cautious when using this option; if used
incorrectly, this option can lead to personal injury or death,
property damage or economic loss.