3 processing after an alarm occurs, 3 processing, 3 processing after an alarm occurs -18 – Yaskawa MP2200 Machine Controller User Manual
Page 482: 1 ) alarm information, 2 ) clearing software limit alarms, Important

9 Utility Functions
9.3.3 Processing after an Alarm Occurs
9-18
The software limit function is enabled only after completing a Zero Point Return or Zero Point
Setting operation.
If any fixed parameters are changed and saved, the Zero Point Return or Zero Point Setting
operation must be performed again.
Disable the software limits in the SERVOPACK.
Σ SERVOPACK: Cn-0014, bits 2 and 3
Σ-ΙΙ or Σ-ΙΙΙ S-ERVOPACK: Pn801.0 = 3 (default value)
9.3.3 Processing after an Alarm Occurs
( 1 ) Alarm Information
If a software limit is exceeded, a Positive/Negative Soft Limit (Positive/Negative Software Limit)
alarm will occur. This alarm can be monitored in the Alarm monitoring parameter (IL04).
( 2 ) Clearing Software Limit Alarms
Clear software limit alarms using the procedure below.
1.
Resetting Alarms
Set the Alarm Clear bit to 1 in the RUN Commands (OW00 bit F) to clear the alarm.
2.
Returning
Use the FEED or STEP command to return past the software limit.
IMPORTANT
Register Number
Name
Contents
IL04
Alarm
Bit 3: Positive Software Limit
Bit 4: Negative Software Limit
Register Number
Name
Contents
OW00
RUN Commands
Bit F: Clear Alarm
Commands will be received in the return direction.
Servo-
motor
An alarm will occur again if a command is
given in the direction of the software limit
that was activated.
Software Limit,
lower limit
Software Limit,
upper limit