5 Motion Commands
5.2.13 Change Speed Loop Gain (KVS)
5-82
5.2.13 Change Speed Loop Gain (KVS)
The KVS command transfers the setting of the Speed Loop Gain (motion setting parameter
OW2F) to the Speed Loop Gain in the SERVOPACK and enables the setting.
( 1 ) Operating Procedure
( 2 ) Holding and Aborting
The Command Pause bit (OB090) and the Command Abort bit (OB091) cannot be used.
( 3 ) Related Parameters
[ a ] Setting Parameters
No.
Execution Conditions
Confirmation Method
1
There are no alarms.
Both IL02 and IL04 are 0.
2
Motion command execution has been completed.
IW08 is 0 and IB090 is OFF.
Execute the
KVS motion command.
• Set OW08 to 14.
• With the MECHATROLINK-II, there is the function that the change of
setting parameter is automatically updated. If utilizing this function,
there is no need to execute KVS command. For details, refer to bit A
(User Constants Self-Writing Function) in Fixed Parameter 1 (Function
Selection 1).
• The Command Pause (OB090) cannot be used.
• The Command Abort (OB091) cannot be used.
The Speed Loop Gain is set in the
SERVOPACK and enabled.
• IW08 will be 14 during command
execution.
• IB090 will be ON during command
execution.
Parameter change completed.
• IW08 will be 14 and IB090 will be
OFF.
Execute NOP motion command.
• Set OW08 to 0.
Parameter
Name
Setting
OW08
Motion Command
The speed loop gain is changed when this parameter is set to 14.
OB090
Command Pause
This parameter is ignored for KVS command.
OB091
Command Abort
This parameter is ignored for KVS command.
OW2F
Speed Loop Gain
Set the gain for the SERVOPACK speed control loop.