8 SVR Virtual Motion Module
8.2.2 Motion Parameter Settings
8-14
( 3 ) Motion Monitoring Parameters
[ a ] Drive Status
[ b ] Over Range Parameter Number
[ c ] Warning
[ d ] Alarm
[ e ] Motion Command Response Code
IW00
Drive Status
Range Unit
−
−
IW00
Bit 0
Motion Controller Operation Ready
Turns ON when the Run Mode (fixed parameter 0) is set to 0 (Normal Running).
OFF: Operation not ready, ON: Operation ready
Bit 1
Running (Servo ON)
OFF: Stopped, ON: Running (Servo ON)
IW01
Over Range Parameter Number
Range
Unit
0 to 65535
−
Stores the number of a parameter set outside the Range .
• Setting parameters: 0 to 999
• Fixed parameters: 1000 or higher
IL02
Warning
Range
Unit
−
−
IL02
Bit 1
Setting Parameter Error
OFF: In Range , ON: Outside Range
Bit 2
Fixed Parameter Error
OFF: In Range , ON: Outside Range
Bit 4
Motion Command Setting Error
OFF: Command setting normal, ON: Command setting error
IL04
Alarm
Range
Unit
−
−
IL04
Bit 5
Servo OFF
OFF: Servo ON, ON: Servo OFF
IW08
Servo Command Type Response
Range
Unit
0 to 65535
−
Stores the motion command code for the command that is being executed.