4.3 SVB-01 Module Parameter Details
4-59
( 18 ) Absolute Infinite Length Axis Position Control Information
( 19 ) Transparent Command Mode
IL5E
Absolute Position at Power OFF (Low Value)
Range
Unit
−2
31
to 2
31
−1
pulse
Stores information used for infinite length axis position control when an absolute encoder is used.
These parameters store the encoder position in 4 words.
IL60
Absolute Position at Power OFF (High Value)
Range
Unit
−2
31
to 2
31
−1
pulse
Same as for IL5E.
IL62
Modularized Position at Power OFF (Low Value)
Range
Unit
−2
31
to 2
31
−1
pulse
Stores information used for infinite length axis position control when an absolute encoder is used.
These parameters store the axis position managed by the Machine Controller in pulses in 4 words.
IL64
Modularized Position at Power OFF (High Value)
Range
Unit
−2
31
to 2
31
−1
pulse
Same as for IL62.
IW70 to
IW7E
Response Buffer for Transparent Command Mode
Range
Unit
−
−
This area is used for response data when MECHATROLINK Servo commands are specified directly.
• MECHATROLINK-I and MECHATROLINK-II, 17-byte Mode: Data area = IW70 to IW77
• MECHATROLINK-II, 32-byte Mode: Data area = IW70 to IW7E