4.3 SVB-01 Module Parameter Details

4-35

( 19 ) Position Complete Timeout

( 20 ) Phase Compensation

OW††26

Position Complete Timeout

Setting Range

Setting Unit

Default Value

0 to 65535

ms

0

Set the time to detect a Positioning Time Over.
If the Positioning Completed bit does not turn ON within the time set here after reference pulses have been distributed during
position control, a Positioning Time Over alarm (monitoring parameter IB††046) will occur. The completion of positioning
will not be checked if this parameter is set to 0.

Position

Phase

Speed

Torque

Speed

Position Error
(IL

1A)

Positioning Completed Width

When this time is longer than the Position
Complete Timeout, a Positioning Time Over
alarm will occur.

Distribution completed

Positioning
Time Over

Position Complete Timeout

OL††28

Phase Compensation

Setting Range

Setting Unit

Default Value

−2

31

to 2

31

−1

Reference unit

0

Set the phase compensation in reference units for phase reference commands.
Use this parameter to compensate for reference pulses in control systems with lower rigidity or gain.
Refer to 5.2.24 Phase References (PHASE) for details on phase reference commands.