Selecting, Separating, and Laying External Cables
• Check the wiring to be sure it has been performed correctly.
There is a risk of motor run-away, injury, or an accident.
• Always use a power supply of the specified voltage.
There is a risk of burning.
• In places with poor power supply conditions, take all steps necessary to ensure that the input power
supply is within the specified voltage range.
There is a risk of device damage.
• Install breakers and other safety measure to provide protection against shorts in external wiring.
There is a risk of fire.
• Provide sufficient shielding when using the MP2200/MP2300 in the following locations.
There is a risk of device damage.
• Noise, such as from static electricity
• Strong electromagnetic or magnetic fields
• Radiation
• Near to power lines
• Consider the following items when selecting the I/O signal lines (external cables) to connect the
MP2200/MP2300 to external devices.
• Mechanical strength
• Noise interference
• Wiring distance
• Signal voltage, etc.
• Separate the I/O signal lines from the power lines both inside and outside the control box to reduce
the influence of noise from the power lines.
If the I/O signal lines and power lines are not separated properly, malfunctioning may result.
CAUTION
CAUTION
鉄板製のセパレータ
ディジタル
入出力信号
ケーブル
一般制御回路
のケーブル
動力回路の
ケーブル
外部配線の分離例
Example of Separated External Cables
Steel separator
Power
circuit
General
control
Digital I/O
signal