4 read servopack parameter (prm_rd), 4 read servopack parameter (prm_rd) -118, 1 ) operating procedure ( 2 ) related parameters – Yaskawa MP2200 Machine Controller User Manual
Page 348

5 Motion Commands
5.3.4 Read SERVOPACK Parameter (PRM_RD)
5-118
5.3.4 Read SERVOPACK Parameter (PRM_RD)
The PRM_RD command reads the setting of the SERVOPACK parameter with the specified
parameter number and parameter size and stores the parameter number in Auxiliary Servo User
Constant Number (monitoring parameter IW37) and the setting in the Auxiliary Servo User
Constant (monitoring parameter IL3A).
The source read data is in the SERVOPACK's RAM.
This command will end with a Command Error End if it is executed with a communication method
other than MECHATROLINK-II (32 byte).
( 1 ) Operating Procedure
( 2 ) Related Parameters
[ a ] Setting Parameters
No.
Execution Conditions
Confirmation Method
1
Motion subcommand execution must be completed.
IW0A is 0 and IB0B0 is OFF.
Execute PRM_RD motion command.
• Set OW0A to 1.
The SERVOPACK parameter is read and stored
in the monitoring parameters.
• IW0A will be 1 during command
execution.
• IB0B0 will be ON during command
processing.
Reading completed.
• IW0A is 1 and IB0B0 is OFF.
Execute NOP motion command.
• Set OW0A to 0.
Parameter
Name
Setting Contents
OW0A
Motion Subcommand
The SERVOPACK parameter is read when this parameter is set to 1.
OW54
Auxiliary Servo User
Constant Number
Set the parameter number of the SERVOPACK parameter to be read.
OW55
Auxiliary Servo
Constant Number Size
Set the size of the SERVOPACK parameter to be read.
Set the size in words.
(
Note) The SERVOPACK's user manual lists the size in bytes,
so those values must be converted to words.