5 Motion Commands
5.2.12 Change Filter Type (CHG_FILTER)
5-80
5.2.12 Change Filter Type (CHG_FILTER)
The CHG_FILTER command enables the current setting of the Filter Type (motion setting parameter
OW03) for execution of the following motion commands: POSING, EX_POSING, ZRET,
INTERPOLATE, LATCH, FEED, and STEP.
Always execute CHG_FILTER command after changing the setting of OW03.
( 1 ) Operating Procedure
( 2 ) Holding and Aborting
The Command Pause bit (OB090) and the Command Abort bit (OB091) cannot be used.
IMPORTANT
No.
Execution Conditions
Confirmation Method
1
There are no alarms.
Both IL02 and IL04 are 0.
2
The Servo ON condition.
IB001 is ON.
3
Pulse distribution has been completed for the
SERVOPACK.
IB0C0 is ON.
4
Motion command execution has been completed.
IW08 is 0 and IB090 is OFF.
Execute the
CHG_FILTER motion command.
• Set OW08 to 13.
• Select one of the following filters:
1.No filter
2.Exponential acceleration/deceleration
3.S-curve acceleration/deceleration (Moving average filter)
• The Command Pause (OB090) cannot be used.
• The Command Abort (OB091) cannot be used.
The Acceleration/Deceleration Filter Type is
enabled.
• IW08 will be 13 during command
execution.
• IB090 will be ON during command
execution.
Command Execution Completed.
• IW08 will be 13 and IB090 will be
OFF.
Execute NOP motion command.
• Set OW08 to 0.