beautypg.com

Pm designer operation manual – B&B Electronics WOP-2121V-N4AE - Manual User Manual

Page 297

background image

4

8

PM Designer Operation Manual

8-21

CHAPTER 8 GRAPHS AND CHARTS

Property

Description

Read Address

Data Type: 32-bit; Number of Data Sets: 1

Word

Description

0,1

Actual number of data points

2,3

Data point 0

4,5

Data point 1

2n+2, 2n+3

Data point n

Data Type: 32-bit; Number of Data Sets: 2

Word

Description

0,1

Actual number of data points

2,3

Data point 0; Data set 1

4,5

Data point 0; Data set 2

6,7

Data point 1; Data set 1

8,9

Data point 1; Data set 2

4n+2, 4n+3

Data point n; Data set 1

4n+4, 4n+5

Data point n; Data set 2

Data Type: 32-bit; Number of Data Sets: 8

Word

Description

0,1

Actual number of data points

2,3

Data point 0; Data set 1

4,5

Data point 0; Data set 2

6,7

Data point 0; Data set 3

8,9

Data point 0; Data set 4

10,11

Data point 0; Data set 5

12,13

Data point 0; Data set 6

14,15

Data point 0; Data set 7

16,17

Data point 0; Data set 8

18,19

Data point 1; Data set 1

20,21

Data point 1; Data set 2

16n+14, 16n+15

Data point n; Data set 7

16n+16, 16n+17

Data point n; Data set 8

Number of Data Sets

Specifies how many data sets that the line chart will read. The line chart displays one line for
each data set. A line chart can display up to 8 lines.

Maximum Number of
Data Points Per Data
Set

Specifies the maximum number of data points that the line chart will read for every data set.
A line chart can display up to 255 data points for one data set.

Note: The actual number of data points for every data set must be specified at runtime. The
actual number must not exceed the maximum number.

Continued