B&B Electronics I-7021_P - Datasheet User Manual
Bit/16-bit analog output module, Specifications, Features/benefits
I-7021/ I-7021P - 5003 1/2
International Headquarters:
707 Dayton Road P.O. Box 1040 Ottawa, IL 61350 USA
815-433-5100 Fax 433-5104 www.bb-elec.com [email protected] [email protected]
Westlink Commercial Park Oranmore Co. Galway Ireland
+353 91 792444 Fax +353 91 792445 www.bb-europe.com [email protected] [email protected]
Integrate – Expand – Simplify
B&B ELECTRONICS
PRODUCT INFORMATION
Cont r ol l er
DAC
GND
+Vs
+V
- V
I sol at i on
Embedded
RS- 485
EEPROM
I-7021/21P
I nt er f ace
Regul at or
Power
Dat a+
Dat a-
+5V
+VOUT
V/ F
Phot o-
Buf f er
- VOUT
Ext . PWR
+I OUT
- I OUT
+V
Models: I-7021, I-7021P
12-bit/16-bit Analog Output Module
I-7000 is a family of network data acquisition and control modules providing analog to digital, digital to
analog, digital input/output, timer/counter and other functions. The modules can be remotely controlled by a
set of commands.
The I-7021 is a single-channel analog output module that uses the D/A converter to convert digital data into
analog output signals with 12-bit resolution and current read-back function. The I-7021P is similar to I-7021
but enhanced to 16 bit resolution.
Specifications
Analog Input
Photo-isolation: 3750 Vrms
Channels: 1
Output type: mA, V
Output range: 0 to 20mA , 4 to 20mA and 0 to 10V
Effective resolution: 12-bit for I-7021, 16-bit for I-7021P
Accuracy: ± 0.1% of FSR for I-7021
± 0.02% of FSR for I-7021P
Read back accuracy: ± 1% of FSR
Resolution: ± 0.02% of FSR for I-7021
± 0.002% of FSR for I-7021P
Zero drift:
Voltage output: ± 30uV/°C for I-7021
± 10uV/°C for I-7021P
Current output: ± 0.2uA/°C
Span temperature
coefficient: ± 25ppm/ °C for I-7021
± 5ppm/ °C for I-7021P
Programmable output slope:
0.125 to 1024 mA/second
0.0625 to 512 V/second
Current load resistance:
Internal power: 500 Ohms
External 24V: 1050 Ohms
Isolation: 3000V DC
Block Diagram
Model I-7021
Features/Benefits
3000VDC isolated analog input
Programmable Power On value
of analog output
Programmable slew rate
Software calibration
Dual watchdog
PIN Assignments
+IOUT
-IOUT
+VOUT
-VOUT
Ext.PWR
INIT*
(Y)DATA+
(G)DATA-
(R)+Vs
(B)GND
1
10