Pm designer operation manual – B&B Electronics WOP-2121V-N4AE - Manual User Manual
Page 255

4
7
PM Designer Operation Manual
7-11
CHAPTER 7 DISPLAYING AND INPUTTING DATA
7.2.4. Advanced Settings
This section describes how to define the advanced settings for a numeric display. The following is an example of the
Advanced page of the Numeric Display property sheet.
The following table describes each property in the Advanced page.
Property
Description
Check this option if you want the value of the monitored variable to be displayed in a
scaled manner. The following is the scaling formula.
Displayed Value = Monitored Value * Gain + Offset
Note: The Gain and Offset are 32-bit floating point numbers. They have at most 6
significant digits. The rounding and truncation may happen.
Gain
The Gain of the scaling formula.
Scaling
Offset
The Offset of the scaling formula.
Check this option if you want the numeric display to display the value with different
color when the value is below the specified low limit or over the specified high limit.
Variable Range
Check this option if the low limit and high limit are specified by the designated
variables at runtime.
Low Limit
Specifies the low limit when the Variable Range is not selected.
When the Variable Range is selected, this property specifies the variable that stores
the low limit at runtime. Click
to enter an address. Click
to select a tag.
High Limit
Specifies the high limit when the Variable Range is not selected.
When the Variable Range is selected, this property specifies the variable that stores
the high limit at runtime. Click
to enter an address. Click
to select a tag.
Text Color
The text color for the high limit.
High
Color
BG Color
The shape’s BG color for the high limit.
Text Color
The text color for the low limit.
Range
Display
Low
Color
BG Color
The shape’s BG color for the low limit.