Pm designer operation manual – B&B Electronics WOP-2121V-N4AE - Manual User Manual
Page 248

7
PM Designer Operation Manual
7-4
CHAPTER 7 DISPLAYING AND INPUTTING DATA
Property
Description
Fractional
Digits
When the Display Type is 32-bit Floating Point, this property specifies the number of fractional digits
to be displayed.
When the Display Type is not 32-bit Floating Point, this property specifies not only the number of
fractional digits to be displayed but also the number of least significant digits to be displayed as the
fractional part. With this feature, an integer can be shown and entered as a fixed point number. When
the Fractional Digits is nonzero, say N, the entered value will be converted to an integer according to
the following formula before being output.
OutputValue = EnteredValue * (Nth power of 10)
Example 1:
Display Type
Total
Digits
Fractional
Digits
Justification
Monitored
Value
Displayed
Value
32-bit Floating Point
4
2
Zero Suppress
12.34
12.34
32-bit Floating Point
4
2
Zero Suppress
123.4
23.40
16-bit Signed Decimal
5
2
Zero Suppress
12345
123.45
16-bit Signed Decimal
5
2
Zero Suppress
-5
-0.05
Example 2:
Display Type
Total
Digits
Fractional
Digits
Entered
Value
Output
Value
32-bit Floating Point
4
2
12.34
12.34
32-bit Floating Point
4
2
123.4
Error!
16-bit Signed Decimal
5
2
123.45
12345
16-bit Signed Decimal
5
2
-0.05
-5
16-bit Signed Decimal
5
2
3
300
Note: This property applies to the display of the initial value, the allowable minimum, and the
allowable maximum on the numeric keypad.
Alignment
The alignment of the displayed value. There are three types of alignment: Left, Center, and Right.
Justification
The justification of the displayed value. There are three types of justification:
Option
Description
Zero Suppress
The leading digits will not display when they are 0.
Leading Zeros
All digits will display.
Leading Spaces
The leading digits will display as blank character when they are 0.
Data Entry
Specifies how to enter a value for the numeric entry at runtime. There are two options:
Option
Description
Pop-up Keypad
You can bring up the keypad by pressing the numeric entry and enter
a value with the keypad.
On-screen Keypad
and/or Function Keys
You can move the cursor by using the function buttons with the
operation of Select Next Data Entry Object or Select Previous Data
Entry Object to select the numeric entry. If there is an on-screen
keypad you can enter a value for the numeric entry right away. You
can also use the function buttons with the operation of Increase Value
By One or Decrease Value By One to change the value of the
destination variable.
當使用常駐式固定鍵盤時,在未按到想要輸入的元件時候是不能輸入的,此時如果直接輸入數值則鍵盤
輸入是無效的,也就是說剛一進入這畫面時,觸控屏系統並不會馬上將第一個數值輸入物件啟用的。客
戶須要先按一下該輸入物件後才啟用固定鍵盤按鈕,也才能使用鍵盤,否則鍵盤是無效的。