I/O compound modules − digital I/O
Four digital outputs 2 A − EPM−S309
l
99
EDSIO1000 EN 7.0
Status displays
Module status LEDs
0
View
Pos.
Designation
Colour
Explanation
1
10
1
RUN
Green
On: Module is ready for operation
2
MF
Red
On: Module error and error at overload, short
circuit, overtemperature (see table below)
3
DO1
Green
On: Digital output triggered
4
DO2
5
DO3
6
DO4
7
−
−
Not assigned
8
9
SLIO001
10
Messages of the status LEDs RUN and MF
RUN
MF
Meaning
On
Off
Module status OK
Bus communication is OK
On
On
Module reports error
Bus communication is OK
Off
On
Module reports error
Bus communication not possible
Off
Off
Error in the bus supply voltage
Blinking
Blinking
Configuration error (
^ 249)
Terminals
Module terminals, spring terminals
1
View
Designation
Explanation
Terminal data
2
6
3
7
4
8
1
5
1
5
4
8
1
Digital output DO1
10 mm
0.08 ... 1.5 mm²
(AWG 28 ... 16)
2
GND
3
Digital output DO3
4
GND
5
Digital output DO2
6
GND
7
Digital output DO4
SLIO002
8
GND
Technical data
EPM−S309: rated data
Module identifier
264
dec
Current consumption/power loss
Current consumption from backplane bus
65 mA
Power loss
0.8 W