beautypg.com

Product description, Status displays, Terminals – Lenze I/O system 1000 System Manual User Manual

Page 99: Technical data

background image

Product description

I/O compound modules − digital I/O

Four digital outputs 2 A − EPM−S309

3

l

99

EDSIO1000 EN 7.0

Status displays

Module status LEDs

0

View

Pos.

Designation

Colour

Explanation

1

10

1

RUN

Green

On: Module is ready for operation

2

MF

Red

On: Module error and error at overload, short
circuit, overtemperature (see table below)

3

DO1

Green

On: Digital output triggered

4

DO2

5

DO3

6

DO4

7

Not assigned

8

9

SLIO001

10

Messages of the status LEDs RUN and MF

RUN

MF

Meaning

On

Off

Module status OK
Bus communication is OK

On

On

Module reports error
Bus communication is OK

Off

On

Module reports error
Bus communication not possible

Off

Off

Error in the bus supply voltage

Blinking

Blinking

Configuration error (

^ 249)

Terminals

Module terminals, spring terminals

1

View

Designation

Explanation

Terminal data

2

6

3

7

4

8

1

5

1

5

4

8

1

Digital output DO1

10 mm

0.08 ... 1.5 mm²

(AWG 28 ... 16)

2

GND

3

Digital output DO3

4

GND

5

Digital output DO2

6

GND

7

Digital output DO4

SLIO002

8

GND

Technical data

EPM−S309: rated data

Module identifier

264

dec

Current consumption/power loss

Current consumption from backplane bus

65 mA

Power loss

0.8 W