Product description

System overview

System design

3

l

23

EDSIO1000 EN 7.0

3.3

System overview

3.3.1

System design

An I/O system 1000 consists of the following modules:

ƒ

An EPM−S1xx bus coupler module
– Connection of the aystem to a fieldbus system (CANopen, PROFIBUS, etc.)
– Integrated DC power supply unit for the supply of the bus coupler module and the

connected I/O compound modules via the backplane bus.

ƒ

Up to 64 EPM−S2xx ... EPM−S6xx I/O compound modules (DI, DO, AI, AO, counter,
etc.)

Bus coupling module

EPM-S1xx

up to 64 I/O compound modules

EPM-S2xx ... EPM-S6xx

electronics supply DC 5 V / 3 A

I/O supply DC 24 V / 7 A *

)

...

DC

2

4

V

/

0

V

DC

2

4

V

/

0

V

SLIO010

Fig. 3−1

Standard design

*)

If no UL conformity is required, the maximum permissible load for the I/O supply is 10 A.