DeviceNet communication

Parameterising technology modules
RS485 interface − EPM−S650

11

l

610

EDSIO1000 EN 7.0

Parameter data STX/ETX protocol

Lenze

Description/value

Name

Pos. in
string of
digits

10

No. of start identifiers

00

h

: 1 start identifier (2. start identifier is ignored)

01

h

: 2 start identifiers

01

h

11

Start identifier 1

ASCII value of the initial character that is sent in
advance of a frame and marks the start of a
transmission.
1 ... 255 (01

h

... FF

h

)

02

h

12

Start identifier 2

ASCII value of the initial character that is sent in
advance of a frame and marks the start of a
transmission.

00

h

13

No. of end identifier

00

h

: 1 end identifier (2. end identifier (0x310D/x) is

ignored)
01

h

: 2 end identifiers

01

h

14

End identifier 1

ASCII value of the end character that is sent after a
frame and marks the end of a transmission.
1 ... 255 (01

h

... FF

h

)

03

h

15

End identifier 2

ASCII value of the end character that is sent after a
frame and marks the end of a transmission.
1 ... 255 (01

h

... FF

h

)

00

h

16

Operating mode

Operating mode of the interface
00

h

: Half duplex − two−wire operation (RS485); the data

are transferred alternately in both directions between
the communication partners.
01

h

: Full duplex − four−wire operation (RS422); the data

are exchanged simultaneously between the
communication partners; transmission and reception
can take place at the same time. Each communication
partner must simultaneously actuate a receive path.
Note: For the "Half duplex" parameterisation under
RS485, no software data flow control is possible.

00

h

17

Cable assignment

For a connection with minimum reflections and the
open circuit detection in RS422/485 operation, the
cables can be pre−assigned via parameters with a
defined idle level (

^ 228).

00

h

: No pre−assignment of the receive path. This

setting is only advisable for special drivers that are
provided with a bus capability.
01

h

: Signal R(A) 5 V (open circuit monitoring); signal

R(B) 0 V. In full duplex operation under RS422, open
circuit monitoring is possible.
02

h

: Signal R(A) 0 V; signal R(B) 5 V. This

pre−assignment corresponds to the idle state (no
transmitter active) in half duplex operation under
RS485. Open circuit monitoring is not possible.

13