PROFIBUS communication

Communication

Acyclic data transfer

9

l

391

EDSIO1000 EN 7.0

9.3.3

Acyclic data transfer

The PROFIBUS−DP−V1 service can be used as an optional extension to enable an acyclic
parameter data transfer. PROFIBUS−DP−V0 and PROFIBUS−DP−V1 may be operated
simultaneously in one network.

The integration of the acyclic service in a fixed bus cycle depends on the correct
configuration of DPM 1:

ƒ

If configured, a time slot is reserved.

ƒ

If not configured, the acyclic service is added when a DP−V1 slave is accessed
acyclically with a DPM 2.

ƒ

The acyclic service always has lower priority.

Parameter data transfer between DPM 1 and slaves

Token

Master 1

(DPM 1)

Master 2

(DPM 2)

Slave 1

Slave 2

Slave 3

epm−t229

Fig. 9−4

Acyclic data transfer

Cyclic process data transfer between DPM 1 and slave 1 ... 3
Acyclic parameter data transfer between DPM 1 and slave 3

1. DPM 1 has the send authorisation (token) and communicates in a fixed sequence

with slave 1, then with slave 2 etc. up to the last slave of the current list via the MS0
channel by means of request and response.

2. DPM 1 transfers the token to DPM 2.

3. During the remaining cycle time (time slot), DPM 2 establishes an acyclical

connection to one of the slaves in order to transmit parameter data via the MS2
channel.

4. At the end of the running cycle time, DPM 2 returns the token to DPM 1.

– Depending on the remaining cycle time, several time slots may be required for the

acyclical data record transfer.

5. Once all of the data records have been transferred, DPM 2 establishes the

connection within one time slot.

)

Note!

DPM 1 can perform the acyclical parameter data exchange via the MS1
channel.