Product description – Lenze I/O system 1000 System Manual User Manual
Page 217
Product description
I/O compound module − pulse width modulation
2 digital outputs with PWM functionality − EPM−S620
l
217
EDSIO1000 EN 7.0
EPM−S620: Rated data
Load voltage
Nominal value
DC 24 (DC 20.4 ... 28.8 V)
Current consumption from load voltage
L+
15 mA (without load)
Total current
for each group, horizontal structure,
40°C
1 A
for each group, horizontal structure,
60°C
1 A
for each group, vertical structure
1 A
Output current
for "1" signal, nominal value
0.5 A
Output delay
from "0" to "1"
Max. 100 ns
from "1" to "0"
Max. 100 ns
Lamp load
10 W
Parallel switching of outputs
for redundant control
Not possible
for power increase
Not possible
Control of a digital input
Possible
Switching frequencies
for ohmic loads
Max. 40 Hz
for inductive loads
Max. 40 Hz
for lamp loads
Max. 40 Hz
Limitation (internal) of the inductive
breaking voltage
L+ (−52 V)
Short circuit protection of the output
Electronically; only highside
Operating threshold of the protection
system
2.5 A
Input data size
4 bytes
Output data size
12 bytes
Status, alarm, diagnostics
Status display
Green LEDs per channel
Alarms
No
Process alarm
No
Diagnostic alarm
No
Diagnostic function
No
Diagnostic information can be read out
Possible
Module status
Green LED
Module error display
Red LED
Channel error display
None
Electrical isolation
Between the channels and the backplane
bus
Yes
Insulation checked with
DC 500 V