beautypg.com

Product description – Lenze I/O system 1000 System Manual User Manual

Page 217

background image

Product description

I/O compound module − pulse width modulation

2 digital outputs with PWM functionality − EPM−S620

3

l

217

EDSIO1000 EN 7.0

EPM−S620: Rated data

Load voltage

Nominal value

DC 24 (DC 20.4 ... 28.8 V)

Current consumption from load voltage
L+

15 mA (without load)

Total current

for each group, horizontal structure,
40°C

1 A

for each group, horizontal structure,
60°C

1 A

for each group, vertical structure

1 A

Output current

for "1" signal, nominal value

0.5 A

Output delay

from "0" to "1"

Max. 100 ns

from "1" to "0"

Max. 100 ns

Lamp load

10 W

Parallel switching of outputs

for redundant control

Not possible

for power increase

Not possible

Control of a digital input

Possible

Switching frequencies

for ohmic loads

Max. 40 Hz

for inductive loads

Max. 40 Hz

for lamp loads

Max. 40 Hz

Limitation (internal) of the inductive
breaking voltage

L+ (−52 V)

Short circuit protection of the output

Electronically; only highside

Operating threshold of the protection
system

2.5 A

Input data size

4 bytes

Output data size

12 bytes

Status, alarm, diagnostics

Status display

Green LEDs per channel

Alarms

No

Process alarm

No

Diagnostic alarm

No

Diagnostic function

No

Diagnostic information can be read out

Possible

Module status

Green LED

Module error display

Red LED

Channel error display

None

Electrical isolation

Between the channels and the backplane
bus

Yes

Insulation checked with

DC 500 V