Ethercat kommunikation, Diagnostics emergency telegram, Manufacturer−specific error codes – Lenze I/O system 1000 System Manual User Manual
Page 555
EtherCAT Kommunikation
Diagnostics
Emergency telegram
l
555
EDSIO1000 EN 7.0
Resulting State
Current State
Description
Code
0x0024
Invalid Input Mapping
P
® S
0x0019
0x0025
Invalid Output Mapping
P
® S
P + E
0x0026
Inconsistent Settings
P
® S
P + E
0x0027
Free−run not supported
P
® S
P + E
0x0028
Synchronization not
supported
P
® S
P + E
0x0029
Free−run needs 3 Buffer
Mode
P
® S
P + E
0x002A
Background Watchdog
S, O
P + E
0x002B
No Valid Inputs and
Outputs
O, S
® O
S + E
0x002C
Fatal Sync Error
O
S + E
0x002D
No Sync Error
S
® O
S + E
0x0030
Invalid DC SYNC
Configuration
O, S
® O, P ® S
P + E, S + E
0x0031
Invalid DC Latch
Configuration
O, S
® O, P ® S
P + E, S + E
0x0032
PLL Error
O, S
® O
S + E
0x0033
DC Sync IO Error
O, S
® O
S + E
0x0034
DC Sync Timeout Error
O, S
® O
S + E
0x0035
DC Invalid Sync Cycle Time P
® S
P + E
0x0036
DC Sync0 Cycle Time
P
® S
P + E
0x0037
DC Sync1 Cycle Time
P
® S
P + E
0x0041
MBX_AOE
B, P, S, O
Current state + E
0x0042
MBX_EOE
B, P, S, O
Current state + E
0x0043
MBX_COE
B, P, S, O
Current state + E
0x0044
MBX_FOE
B, P, S, O
Current state + E
0x0045
MBX_SOE
B, P, S, O
Current state + E
0x004F
MBX_VOE
B, P, S, O
Current state + E
0x0050
EEPROM No Access
Any
Any + E
0x0051
EEPROM Error
Any
Any + E
0x0060
Coupler Restarted Locally
Any
I
< x8000
Reserved
Manufacturer−specific error codes
Code
Description
Current State
Resulting State
0x8000
no module recognized or
present
I
I + E
0x8001
Module at system bus
needs update
P > S
P + E
0x8002
Init error
P > S
PO + E
0x8003
unexpected restart
(Watchdog)
P > S
PO + E