CANopen communication
Setting the parameters of analog I/O
2 analog inputs −10 ... +10 V (16 bits) − EPM−S406
l
290
EDSIO1000 EN 7.0
8.8.5
2 analog inputs −10 ... +10 V (16 bits) − EPM−S406
Parameter data
Index/sub
index
Name
Description/value
Lenze
0x3100/x Diagnostics
Bits 0 ... 5: Reserved
Bit 6: Diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved
00
h
0x3101/x Reserved
0
0x3102/x Limit value
monitoring
Bit 0: Channel 1 (0 = inhibited; 1 = enabled)
Bit 1: Channel 2 (0 = inhibited; 1 = enabled)
Bits 7 ... 2: Reserved
00
h
0x3103/x Interference
frequency
suppression
Bit 1, 0: Channel 1
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 3, 2: Channel 2
00: Deactivated
01: 60 Hz
10: 50 Hz
Bits 7 ... 4: Reserved
00
h
0x3104/x Function channel 1
12 (12
h
): −10 ... 10 V / −27648 ... 27648
dec
34 (22
h
): −10 ... 10 V / −16384 ... 16384
dec
16 (10
h
): 0 ... 10 V / 0 ... 27648
dec
32 (20
h
): 0 ... 10 V / 0 ... 16384
dec
255 (FF
h
): channel deactivated
20
h
0x3105/x Reserved
0
0x3106/x
0x3107/x
Upper limit value
channel 1
Value from the rated range; if this value is exceeded and the
limit value monitoring function is enabled, a process alarm is
triggered.
7FFF
h
: Limit value alarm deactivated
7FFF
h
0x3108/x
0x3109/x
Lower limit value
channel 1
Value from the rated range; if the actual value falls below this
value and the limit value monitoring function is enabled, a
process alarm is triggered.
8000
h
: Limit value alarm deactivated
8000
h
0x310A/x Function channel 2
12 (12
h
): −10 ... 10 V / −27648 ... 27648
dec
34 (22
h
): −10 ... 10 V / −16384 ... 16384
dec
16 (10
h
): 0 ... 10 V / 0 ... 27648
dec
32 (20
h
): 0 ... 10 V / 0 ... 16384
dec
255 (FF
h
): channel deactivated
20
h
0x310B/x Reserved
0
0x310C/x
0x310D/x
Upper limit value
channel 2
Value from the rated range; if this value is exceeded and the
limit value monitoring function is enabled, a process alarm is
triggered.
7FFF
h
: Limit value alarm deactivated
7FFF
h
0x310E/x
0x310F/x
Lower limit value
channel 2
Value from the rated range; if the actual value falls below this
value and the limit value monitoring function is enabled, a
process alarm is triggered.
8000
h
: Limit value alarm deactivated
8000
h
With the formulas listed in the following you can convert a digital value into an analog
output value and vice versa.