Product description – Lenze I/O system 1000 System Manual User Manual
Page 178
Product description
I/O compound modules − counter
Two counters 32 bits, 24 V DC − EPM−S601
l
178
EDSIO1000 EN 7.0
Counting continuously
Limits
Counting range
Lower counting limit
−2 147 483 648 (−2
31
)
Upper counting limit
+2 147 483 647 (2
31
−1)
Function:
ƒ
For starting the counting process the internal gate has to be opened.
– The counter counts from the loading value in the counting range.
– If the counter reaches the upper counting limit when counting forwards, and if a
further count pulse in positive direction occurs, the counter skips to the lower
counting limit and continues to count from there.
– If the counter reaches the lower counting limit when counting backwards, and if a
further negative count pulse occurs, the counter skips to the upper counting limit
and continues to count from there.
– If maximum values are exceeded or minimum values are not reached, the status
bits STS_OFLW or STS_UFLW are set. These bits remain set until they are reset with
RES_SET in the control word. If enabled, additionally a process alarm is triggered.
ƒ
For stopping the counting process the internal gate has to be closed.
Upper counting
limit value
Lower counting
limit value
Loaded value
0
Counter starts
Counter stops
Overflow
Underflow
Time
Counter content
SLIO030
Fig. 3−51
Example of "Counting continuously"