Product description

I/O compound modules − counter
Two counters 32 bits, 24 V DC − EPM−S601

3

l

178

EDSIO1000 EN 7.0

Counting continuously

Limits

Counting range

Lower counting limit

−2 147 483 648 (−2

31

)

Upper counting limit

+2 147 483 647 (2

31

−1)

Function:

ƒ

For starting the counting process the internal gate has to be opened.
– The counter counts from the loading value in the counting range.
– If the counter reaches the upper counting limit when counting forwards, and if a

further count pulse in positive direction occurs, the counter skips to the lower
counting limit and continues to count from there.

– If the counter reaches the lower counting limit when counting backwards, and if a

further negative count pulse occurs, the counter skips to the upper counting limit
and continues to count from there.

– If maximum values are exceeded or minimum values are not reached, the status

bits STS_OFLW or STS_UFLW are set. These bits remain set until they are reset with
RES_SET in the control word. If enabled, additionally a process alarm is triggered.

ƒ

For stopping the counting process the internal gate has to be closed.

Upper counting

limit value

Lower counting

limit value

Loaded value

0

Counter starts

Counter stops

Overflow

Underflow

Time

Counter content

SLIO030

Fig. 3−51

Example of "Counting continuously"