EtherCAT Kommunikation
Setting the parameters of analog I/O
4 analog inputs 0/4 ... 20 mA (12 bits) − EPM−S403
l
489
EDSIO1000 EN 7.0
10.5.4
4 analog inputs 0/4 ... 20 mA (12 bits) − EPM−S403
Parameter data
Subindex
Name
Description/value
Lenze
01
Function channel 1
48 (30
h
): 4 ... 20 mA / 0 ... 27648
dec
64 (40
h
): 4 ... 20 mA / 0 ... 16384
dec
49 (31
h
): 0 ... 20 mA / 0 ... 27648
dec
65 (41
h
): 0 ... 20 mA / 0 ... 16384
dec
255 (FF
h
): channel deactivated
31
h
02
Function channel 2
31
h
03
Function channel 3
31
h
04
Function channel 4
31
h
With the formulas listed in the following you can convert a digital value into an analog
output value and vice versa.
Measuring range
Current (I)
Decimal (D)
Hex
Range
Conversion
(Fct. no.)
[mA]
0 ... 20 mA
(31
h
)
23.52
32511
7EFF
Overflow
I = D * 20 / 27648
D = 27648 * I / 20
20
27648
6C00
Nominal range
10
13824
3600
0
0
0000
Not possible, is limited to 0 mA
Underflow
0 ... 20 mA
(41
h
)
25
20480
5000
Overflow
I = D * 20 / 16384
D = 16384 * I / 20
20
16384
4000
Nominal range
10
8192
2000
0
0
0000
Not possible, is limited to 0 mA
Underflow
4 ... 20 mA
(30
h
)
22.81
32511
7EFF
Overflow
I = D * 16 / 27648 + 4
D = 27648 * (I−4) / 16
20
27648
6C00
Nominal range
12
13824
3600
4
0
0000
0
−6912
E500
Underflow
4 ... 20 mA
(40
h
)
24
20480
5000
Overflow
I = D * 16 / 16384 + 4
D = 16384 * (I−4) / 16
20
16384
4000
Nominal range
12
8192
2000
4
0
0000
0
−4096
F000
Underflow