Access to the I/O system 1000
Access to I/O area

12

l

618

EDSIO1000 EN 7.0

12.2.1

Access to I/O area

With PROFINET, the input/output range is automatically shown in the corresponding
address range of the master system. The following index no. also provides access to the I/O
ranges:

ƒ

Index = 8028h: Reading of the input data (slot 1 ... 64)

ƒ

Index = 8029h: Reading of the output data (slot 1 ... 64)

12.2.2

Access to parameter data

The GSDML file serves to set parameter data for the corresponding modules via the
hardware configuration. When the I/O device starts, the parameter data is given once to
the modules via the I/O controller. After writing, the parameter data in the module is
active.

Access to

Slot

Index

All parameters of the PROFINET coupler incl. header (4 bytes)

0

007D

h

All parameters of the PROFINET coupler

0

007E

h

All module parameters incl. header (4 bytes)

1 ... 64

007D

h

Data record DS 00

h

of the module parameters

1 ... 64

007E

h

Data record DS 01

h

of the module parameters

1 ... 64

007F

h

Data record DS 80

h

... 90

h

of the module parameters

1 ... 64

0080

h

...0090

h