PROFINET communication
Access to the I/O system 1000
Access to I/O area
l
618
EDSIO1000 EN 7.0
12.2.1
Access to I/O area
With PROFINET, the input/output range is automatically shown in the corresponding
address range of the master system. The following index no. also provides access to the I/O
ranges:
ƒ
Index = 8028h: Reading of the input data (slot 1 ... 64)
ƒ
Index = 8029h: Reading of the output data (slot 1 ... 64)
12.2.2
Access to parameter data
The GSDML file serves to set parameter data for the corresponding modules via the
hardware configuration. When the I/O device starts, the parameter data is given once to
the modules via the I/O controller. After writing, the parameter data in the module is
active.
Access to
Slot
Index
All parameters of the PROFINET coupler incl. header (4 bytes)
0
007D
h
All parameters of the PROFINET coupler
0
007E
h
All module parameters incl. header (4 bytes)
1 ... 64
007D
h
Data record DS 00
h
of the module parameters
1 ... 64
007E
h
Data record DS 01
h
of the module parameters
1 ... 64
007F
h
Data record DS 80
h
... 90
h
of the module parameters
1 ... 64
0080
h
...0090
h