DeviceNet communication
Parameterising the temperature measurement
Two analog inputs for thermocouple measurement − EPM−S405
l
583
EDSIO1000 EN 7.0
Range
Measured value
Measuring range
Range
[K]
[°F]
[°C]
(Fct. no.)
Type N:
−270 ... +1300 °C
−454 ... 2372 °F
0 ... 1573.2 K
(B2
h
: ext. comp. 0 °C)
(C2
h
: int. comp. 0 °C)
+15500
28220
18232
Overflow
−2700 ... +13000
−4540 ... 23720
0 ... 15732
Nominal range
−
−
−
Underflow
Type R:
−50 ... +1769 °C
−58 ... 3216.2 °F
223.2 ... 2042.2 K
(B3
h
: ext. comp. 0 °C)
(C3
h
: int. comp. 0 °C)
+20190
32766
22922
Overflow
−500 ... +17690
−580 ... 32162
2232 ... 20422
Nominal range
−1700
−2740
1032
Underflow
Type S:
−50 ... +1769 °C
−58 ... 3216.2 °F
223.2 ... 2042.2 K
(B4
h
: ext. comp. 0 °C)
(C4
h
: int. comp. 0 °C)
+20190
32766
22922
Overflow
−500 ... +17690
−580 ... 32162
2232 ... 20422
Nominal range
−1700
−2740
1032
Underflow
Type T:
−270 ... +440 °C
−454 ... 752 °F
3.2 ... 673.2 K
(B2
h
: ext. comp. 0 °C)
(C2
h
: int. comp. 0 °C)
+5400
10040
8132
Overflow
−2700 ... +4000
−4540 ... 7520
32 ... 6732
Nominal range
−
−
−
Underflow
Type B:
0 ... +1820 °C
32 ... 2786.5 °F
273.2 ... 2093.2 K
(B6
h
: ext. comp. 0 °C)
(C6
h
: int. comp. 0 °C)
+20700
32766
23432
Overflow
0 ... +18200
320 ... 27865
2732 ... 20932
Nominal range
−1200
−1840
1532
Underflow
Type C:
0 ... +2315 °C
32 ... 2786.5 °F
273.2 ... 2093.2 K
(B7
h
: ext. comp. 0 °C)
(C7
h
: int. comp. 0 °C)
+25000
32766
23432
Overflow
0 ... +23150
320 ... 27865
2732 ... 20932
Nominal range
−1200
−1840
1532
Underflow
Type E:
−270 ... +1000 °C
−454 ... 1832 °F
0 ... 1273.2 K
(B8
h
: ext. comp. 0 °C)
(C8
h
: int. comp. 0 °C)
+12000
21920
14732
Overflow
−2700 ... +10000
−4540 ... 18320
0 ... 12732
Nominal range
−
−
−
Underflow
Type L:
−200 ... +900 °C
−328 ... 1652 °F
73.2 ... 1173.2 K
(B9
h
: ext. comp. 0 °C)
(C9
h
: int. comp. 0 °C)
+11500
21020
14232
Overflow
−2000 ... +9000
−3280 ... 16520
732 ... 11732
Nominal range
−
−
−
Underflow