PROFIBUS communication

Parameterising technology modules

2 digital outputs with PWM functionality − EPM−S620

9

l

465

EDSIO1000 EN 7.0

Control word PWMPDx

Bit

Name

Function

0

Reserved

1

CTRL_OUTBV

PWM output response
0: push/pull output

Push/pull mode should be used if you need defined high/low levels for
a rapid change. This is used with a low load especially if "highside"
mode cannot move the output to low fast enough during a low status.
With push/pull, the output is switched to ground with low active and
to voltage with high active.

1: highside output

In highside mode, the output switched to low remains in a state of
uncertainty between ground and voltage. The load has to "pull" itself
to ground. In highside mode, the switch is only made to high level
active.

3 ... 7

Reserved

8

CTRL_STRT

Edge 0−1 starts PWM output on channel x

9

CTRL_STP

Edge 0−1 stops PWM output on channel x

10 ... 15

Reserved

Parameter data

Data set

Name

Description/value

Lenze

No.

Byte

80

h

0

PWM 1: period

Set parameters here for the total time for pulse duration
and pulse pause. The time should be selected as a factor
for the 20.83 ns basis.
Values below 25

ms are ignored. If the pulse duration is

higher or equal to the period, the DO output is set
permanently.
Value range: 1200 ... 8388607 (25

ms ... approx. 175 ms)

1F40

h

81

h

0

PWM 2: Period

1F40

h

Diagnostic data

Since this module does not support alarms, the diagnostic data provides information