Product description
Bus coupler modules
PROFIBUS − EPM−S120
l
43
EDSIO1000 EN 7.0
EPM−S120: Rated data
Communication
Fieldbus
PROFIBUS−DP in accordance with EN 50170
Physics
RS485 insulated
Connection
9−pole Sub−D socket
Topology
Linear bus with bus termination at both ends
Electrical isolation
Yes
Nodes
Number, max.
125
Address
1 ... 125
Transmission speed
9.6 kbps ... 12 Mbps
Process data for PROFIBUS−DP−V0
Input data, max.
244 bytes
Output data, max.
244 bytes
Process data for PROFIBUS−DP−V1
Input data, max.
240 bytes
Output data, max.
240 bytes
Parameter data, max. length *
224 bytes
the amount required by an I/O module with ...
digital inputs or outputs (EPM−S200 ...
EPM−S305)
0 bytes
2 analog inputs (EPM−S400/−S402)
6 bytes
4 analog inputs (EPM−S401/−S403)
8 bytes
2 analog outputs (EPM−S500/−S502)
8 bytes
4 analog outputs (EPM−S501/−S503)
10 bytes
4 analog inputs res. (EPM−S404)
34 bytes
2 analog inputs TE (EPM−S405)
22 bytes
1 counter 32 bits, 24 V DC (EPM−S600)
21 bytes
2 counters 32 bits, 24 V DC (EPM−S601)
42 bytes
1 counter 32 bits, 5 V DC (EPM−S602)
22 bytes
2 counters 32 bits, 24 V DC (EPM−S603)
8 bytes
SSI (EPM−S604)
33 bytes
2 dig. inputs, time stamp (EPM−S207)
6 bytes
2 dig. outputs, time stamp (EPM−S310)
2 bytes
2 dig. outputs, PWM (EPM−S620)
8 bytes
RS232 interface (EPM−S640)
8/20/60 bytes (parameterisable)
*
Calculation example: 5 x EPM−S400 and 5 x EPM−S501
® (5 x 6 bytes) + (5 x 10 bytes) = 80 bytes; i.e. a reserve of
144 bytes