PROFINET communication

Parameterising the counter
One counter 32 bits, 5 V DC − EPM−S602

12

l

680

EDSIO1000 EN 7.0

Process alarm

A process alarm causes a call of the OB 40. Within the OB 40 you have the possibility of
determining the logic basic address of the module that has triggered the process alarm via
the local word 6. Further information on the triggering event can be found in the "Local
double word 8".

Local double word 8 of OB 40:

Local byte

Bit 7 ... 0

8

Bit 0: 0
Bit 1: 0
Bit 2: Counter 0, overflow/underflow/final value
Bit 3: Counter 0, comparison value reached
Bit 4: 0
Bit 5: 0
Bit 6: Counter 1, overflow/underflow/final value
Bit 7: Counter 1, comparison value reached

9

State of the inputs at the time of the alarm
Bit 0: Counter 0, A/pulse
Bit 1: Counter 0, B/direction
Bit 2: Counter 1, A/pulse
Bit 3: Counter 1, B/direction
Bit 7 ... 4: 0 (fixed)

10 ... 11

16 bit

ms value at the time of the alarm

Ticker value: After mains connection a timer (

ms ticker) is started, which after 65535 ms

starts with 0 again. With every change of the count value the time value of the timer is
stored as 16−bit

ms value together with the count value in the input area.