DeviceNet communication
Parameterising the encoder evaluation
SSI − EPM−S604
l
598
EDSIO1000 EN 7.0
Lenze
Description/value
Name
Pos. in
string of
digits
7
Bit 1 ... 0: ready for operation
During "Monitoring operation" the module serves to monitor
the data exchange between an SSI master and an SSI encoder.
It receives the cycle by the master and the data flow by the
SSI encoder.
In the "Master mode" operating mode the module provides a
cycle to the encoder and receives data by the encoder.
01
b
= monitoring operation
10
b
= master mode
Bit 2: shifting direction
Specify the orientation of the encoder data here. More
information can be found in the data sheet for your encoder.
Usually, the SSI encoder uses "MSB first".
0 = LSB first (LSB is transmitted first)
1 = MSB first (MSB is transmitted first)
Bit 3: edge clock signal
Here you can specify the edge type of the clock signal, in the
case of which the encoder supplies data. Information on this
can be found in the data sheet for your encoder. Usually the
SSI encoders respond to rising edges.
0 = falling edge
1 = rising edge
Bit 4: coding
In the "Binary code" setting, the provided encoder value
remains unchanged. In the "Gray code" setting, the
gray−coded value provided by the encoder is converted into a
binary value. Only after this conversion, the received encoder
value is scaled, if required. The Gray code is another form of
representation of the binary code. It is based on the fact that
two adjacent Gray numbers differ from each other in exactly
one bit. If the Gray code is used, transmission errors can be
easily detected, since adjacent characters must only differ
from each other in one digit. Information on this can be
found in the data sheet for your encoder.
0 = standard code
1 = Gray code
Bits 7 ... 5: reserved
1E
h
8
Reserved
9
SSI function
By enabling the SSI function the module starts with the cycle
output and the evaluation of the encoder data. In the "monitor
operation" mode, the module starts with the encoder
evaluation.
0 (00
h
) = inhibited
1 (01
h
) = enabled
00