Profinet communication – Lenze I/O system 1000 System Manual User Manual
Page 672
PROFINET communication
Parameterising the counter
Two counters 32 bits, 24 V DC − EPM−S601
l
672
EDSIO1000 EN 7.0
Lenze
Description/value
Name
Data set
Lenze
Description/value
Name
Byte
No.
81
h
0...3
Set value counter 1
Counting method:
0x3111: byte 3 (high byte)
0x3112: byte 2
0x3113: byte 1
0x3114: byte 0 (low byte)
00
h
4...7
Final value counter 1
Counting method:
0x310D: byte 3 (high byte)
0x310E: byte 2
0x310F: byte 1
0x3110: byte 0 (low byte)
00
h
8...11 Loading value
counter 1
Counting method:
0x3109: byte 3 (high byte)
0x310A: byte 2
0x310B: byte 1
0x310C: byte 0 (low byte)
00
h
12
Hysteresis counter 1
The hysteresis for instance serves to avoid frequent
switching operations of the output and/or triggering of
the alarm when the count value is within the range of the
comparison value. For the hysteresis you can select a
range between 0 and 255. With the settings 0 and 1 the
hysteresis is switched off.
The hysteresis has an effect on the zero crossing,
comparison, overflow/underflow.
00
h
13
Reserved
82
h
0
Alarm response
counter 2
See counter 1
00
h
1
Counter function
counter 2
See counter 1
00
h
2
Comparator
counter 2
See counter 1
00
h
3
Signal evaluation
counter 2
See counter 1
00
h
83
h
0...3
Set value counter 2
See counter 1
00
h
4...7
Final value counter 2
See counter 1
00
h
8...11 Loading value
counter 2
See counter 1
00
h
12
Hysteresis counter 2
See counter 1
00
h