PROFINET communication

Setting the parameters of analog I/O

2 analog inputs 0/4 ... 20 mA (16 bits) − EPM−S408

12

l

637

EDSIO1000 EN 7.0

12.6.6

2 analog inputs 0/4 ... 20 mA (16 bits) − EPM−S408

Parameter data

During the execution time you can access the parameter data via the following data sets:

Data set

Name

Description/value

Lenze

No.

Byte

0

Diagnostics

Bits 0 ... 5: Reserved
Bit 6: Diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved

00

h

Reserved

0

Limit value
monitoring

Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: Reserved

00

h

1

Interference
frequency suppression

Bit 1, 0: Channel 1

00: Deactivated
01: 60 Hz
10: 50 Hz

Bit 3, 2: Channel 2

00: Deactivated
01: 60 Hz
10: 50 Hz

Bits 7 ... 4: Reserved

00

h

128

Function channel 1

48 (30

h

): 4 ... 20 mA / 0 ... 27648

dec

64 (40

h

): 4 ... 20 mA / 0 ... 16384

dec

49 (31

h

): 0 ... 20 mA / 0 ... 27648

dec

65 (41

h

): 0 ... 20 mA / 0 ... 16384

dec

255 (FF

h

): channel deactivated

41

h

Reserved

0

Upper limit value
channel 1

Value from the rated range; if this value is exceeded and
the limit value monitoring function is active, a process
alarm is triggered.
7FFF

h

: Limit value alarm deactivated

7FFF

h

Lower limit value
channel 1

Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is
active, a process alarm is triggered.
8000

h

: Limit value alarm deactivated

8000

h

129

Function channel 2

48 (30

h

): 4 ... 20 mA / 0 ... 27648

dec

64 (40

h

): 4 ... 20 mA / 0 ... 16384

dec

49 (31

h

): 0 ... 20 mA / 0 ... 27648

dec

65 (41

h

): 0 ... 20 mA / 0 ... 16384

dec

255 (FF

h

): channel deactivated

41

h

Reserved

0

Upper limit value
channel 2

Value from the rated range; if this value is exceeded and
the limit value monitoring function is active, a process
alarm is triggered.
7FFF

h

: Limit value alarm deactivated

7FFF

h

Lower limit value
channel 2

Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is
active, a process alarm is triggered.
8000

h

: Limit value alarm deactivated

8000

h

With the formulas listed in the following you can convert a digital value into an analog
output value and vice versa.