6 2 analog inputs 0/4 ma (16 bits) - epm-s408, 2 analog inputs 0/4 ma (16 bits) − epm−s408, Profinet communication – Lenze I/O system 1000 System Manual User Manual
Page 637
PROFINET communication
Setting the parameters of analog I/O
2 analog inputs 0/4 ... 20 mA (16 bits) − EPM−S408
l
637
EDSIO1000 EN 7.0
12.6.6
2 analog inputs 0/4 ... 20 mA (16 bits) − EPM−S408
Parameter data
During the execution time you can access the parameter data via the following data sets:
Data set
Name
Description/value
Lenze
No.
Byte
0
Diagnostics
Bits 0 ... 5: Reserved
Bit 6: Diagnostic alarm (0 = inhibited; 1 = enabled)
Bit 7: Reserved
00
h
Reserved
0
Limit value
monitoring
Bit 0: Channel 1 (0 = deactivated; 1 = activated)
Bit 1: Channel 2 (0 = deactivated; 1 = activated)
Bits 7 ... 2: Reserved
00
h
1
Interference
frequency suppression
Bit 1, 0: Channel 1
00: Deactivated
01: 60 Hz
10: 50 Hz
Bit 3, 2: Channel 2
00: Deactivated
01: 60 Hz
10: 50 Hz
Bits 7 ... 4: Reserved
00
h
128
Function channel 1
48 (30
h
): 4 ... 20 mA / 0 ... 27648
dec
64 (40
h
): 4 ... 20 mA / 0 ... 16384
dec
49 (31
h
): 0 ... 20 mA / 0 ... 27648
dec
65 (41
h
): 0 ... 20 mA / 0 ... 16384
dec
255 (FF
h
): channel deactivated
41
h
Reserved
0
Upper limit value
channel 1
Value from the rated range; if this value is exceeded and
the limit value monitoring function is active, a process
alarm is triggered.
7FFF
h
: Limit value alarm deactivated
7FFF
h
Lower limit value
channel 1
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is
active, a process alarm is triggered.
8000
h
: Limit value alarm deactivated
8000
h
129
Function channel 2
48 (30
h
): 4 ... 20 mA / 0 ... 27648
dec
64 (40
h
): 4 ... 20 mA / 0 ... 16384
dec
49 (31
h
): 0 ... 20 mA / 0 ... 27648
dec
65 (41
h
): 0 ... 20 mA / 0 ... 16384
dec
255 (FF
h
): channel deactivated
41
h
Reserved
0
Upper limit value
channel 2
Value from the rated range; if this value is exceeded and
the limit value monitoring function is active, a process
alarm is triggered.
7FFF
h
: Limit value alarm deactivated
7FFF
h
Lower limit value
channel 2
Value from the rated range; if the actual value falls below
this value and the limit value monitoring function is
active, a process alarm is triggered.
8000
h
: Limit value alarm deactivated
8000
h
With the formulas listed in the following you can convert a digital value into an analog
output value and vice versa.