5 devicenet - epm-s150, Devicenet − epm−s150, Product description – Lenze I/O system 1000 System Manual User Manual
Page 54
![background image](/manuals/565636/54/background.png)
Product description
Bus coupler modules
DeviceNet − EPM−S150
l
54
EDSIO1000 EN 7.0
3.5.5
DeviceNet − EPM−S150
The bus coupler module represents the interface between the process level (I/O level) and
the higher−level fieldbus. The control signals on the process level are transmitted by the I/O
compound modules via the internal backplane bus.
Features
ƒ
DeviceNet coupler
ƒ
Up to 64 I/O compound modules can be connected to a DeviceNet bus coupler
module
ƒ
Group 2 only Device uses Predefined Connection Set
ƒ
Poll only Device
– No operating mode BIT STROBE
– NO operating mode CHANGE OF STATE
– Profile Generic Device
ƒ
Support of all baud rates: 125, 250 und 500 kbps
ƒ
Max. 255 bytes input/output data
ƒ
Integrated power supply unit for the internal voltage supply and the voltage supply
of the connected I/O compound modules
– Power supply unit supplied via an external DC voltage source
ƒ
Connection to the DeviceNet via "Open Style Connector"
ƒ
Setting of the DeviceNet address and the baud rate via coding switch
ƒ
LEDs for status display