beautypg.com

5 devicenet - epm-s150, Devicenet − epm−s150, Product description – Lenze I/O system 1000 System Manual User Manual

Page 54

background image

Product description

Bus coupler modules
DeviceNet − EPM−S150

3

l

54

EDSIO1000 EN 7.0

3.5.5

DeviceNet − EPM−S150

The bus coupler module represents the interface between the process level (I/O level) and
the higher−level fieldbus. The control signals on the process level are transmitted by the I/O
compound modules via the internal backplane bus.

Features

ƒ

DeviceNet coupler

ƒ

Up to 64 I/O compound modules can be connected to a DeviceNet bus coupler
module

ƒ

Group 2 only Device uses Predefined Connection Set

ƒ

Poll only Device
– No operating mode BIT STROBE
– NO operating mode CHANGE OF STATE
– Profile Generic Device

ƒ

Support of all baud rates: 125, 250 und 500 kbps

ƒ

Max. 255 bytes input/output data

ƒ

Integrated power supply unit for the internal voltage supply and the voltage supply
of the connected I/O compound modules
– Power supply unit supplied via an external DC voltage source

ƒ

Connection to the DeviceNet via "Open Style Connector"

ƒ

Setting of the DeviceNet address and the baud rate via coding switch

ƒ

LEDs for status display