I/O compound modules − temperature measurement
Two analog inputs for thermocouple measurement − EPM−S405
l
155
EDSIO1000 EN 7.0
EPM−S405: Rated data
Thermocouple inputs
Thermocouple ranges
Types B, C, E, J, K, L, N, R, S, T
Operational error limit
With interference frequency suppression:
Types E, L, T, J, K, N:
± 1.5 K
Types B, C, R, S:
± 4.0 K
Without interference frequency suppression:
Types E, L, T, J, K, N:
± 2.5 K
Types B, C, R, S:
± 8.0 K
Basic error limit
With interference frequency suppression:
Types E, L, T, J, K, N:
± 1.0 K
Types B, C, R, S:
± 3.0 K
Without interference frequency suppression:
Types E, L, T, J, K, N:
± 2.0 K
Types B, C, R, S:
± 7.0 K
Measuring principle
Sigma−delta
Resolution
16 bits
Basic conversion time
4.2 ... 324.1 ms (50 Hz) per channel
3.8 ... 270.5 ms (60 Hz) per channel
Interference voltage suppression for a
frequency of
> 90 dB at 50 Hz (UCM < 10 V)
Temperature error
(relating to input range)
± 0.001 %/K
Linearity distortion
(relating to input range)
± 0.005 %
Repeat accuracy (in steady−state vibration at
25°C, relating to the input range)
± 0.05 %
Temperature error of the internal
compensation
± 0.2 %
Temperature compensation
parameterisable
Yes
external
Yes
internal
Yes
Input data size
4 bytes
Status, alarm, diagnostics
Status display
Yes
Alarms
Yes
Process alarm
Yes, parameterisable
Diagnostic alarm
Yes, parameterisable
Diagnostic function
Yes
Diagnostic information can be read out
Possible
Module status
Green LED
Module error display
Red LED
Channel error display
Red LEDs per channel
Electrical isolation
Between the channels and the backplane
bus
Yes
Between the channels and the voltage
supply
Yes
Max. potential difference between inputs
(U
cm
)
DC 140 V / AC 60 V
Max. potential difference between inputs
and M
internal
(U
iso
)
DC 75 V / AC 60 V
Insulation checked with
DC 500 V