2 rs485 interface - epm-s650, Rs485 interface − epm−s650, Product description – Lenze I/O system 1000 System Manual User Manual
Page 224
Product description
I/O compound modules − communication
RS485 interface − EPM−S650
l
224
EDSIO1000 EN 7.0
3.12.2
RS485 interface − EPM−S650
This module can be used to communicate with field devices via an RS422 or RS485
interface. For access to devices with an RS422/RS485 interface, the protocol of the field
device must be implemented in the control system in each case.
The following handling blocks are provided:
IPC / control
Programming via
Bus system
Handling block
Lenze Industrial PC
l
EL 1800−9800
l
CS 5800−9800
l
CPC 2800
PLC Designer V2
l
CAN
l
EtherCAT
l
PROFIBUS
Data reception:
L_IO1000_EPMS640/650_RS232/485Write
Data transmission:
L_IO1000_EPMS640/650_RS232/485Read
L−force Controller
3200 C
PLC Designer V3
,
Further information on the subject ...
ƒ
"Serial process interfacing with I/O compound modules", see appendix.
ƒ
"Parameterisation", see in the corresponding chapter for the fieldbuses.
ƒ
"Handling blocks", see documentation for the PLC Designer.
Features
ƒ
Serial RS422/RS485 interface (isolated from the backplane bus)
ƒ
Transmission speed 150 bps ... 115.2 kbps
ƒ
Protocols
– ASCII
– STX/ETX
– 3964(R)
ƒ
Up to 250 frames (1024 bytes of receive or transmit buffer)
ƒ
Character delay time can be parameterised in ms grid
ƒ
Parameter setting via 19 bytes of parameter data
)
Note!
More information can be found in the "Communication" chapter.