PROFINET communication
Setting the parameters of analog I/O
4 analog inputs 0 ... 10 V (12 bits) − EPM−S401
l
628
EDSIO1000 EN 7.0
12.6.2
4 analog inputs 0 ... 10 V (12 bits) − EPM−S401
Parameter data
During the execution time you can access the parameter data via the following data sets:
Data set
Name
Description/value
Lenze
No.
Byte
128
0
Function channel 1
16 (10
h
): 0 ... 10 V / 0 ... 27648
dec
32 (20
h
): 0 ... 10 V / 0 ... 16384
dec
255 (FF
h
): channel deactivated
10
h
129
0
Function channel 2
10
h
130
0
Function channel 3
10
h
131
0
Function channel 4
10
h
With the formulas listed in the following you can convert a digital value into an analog
output value and vice versa.
Measuring range
Voltage (U)
Decimal (D)
Hex
Range
Conversion
(Fct. no.)
[V]
0 ... 10 V
(10
h
)
11.76
32511
7EFF
Overflow
U = D * 10 / 27648
D = 27648 * U / 10
10
27648
6C00
Nominal range
5
13824
3600
0
0
0000
Not possible, is limited to 0 V
Underflow
0 ... 10 V
(20
h
)
12.5
20480
5000
Overflow
U = D * 10 / 16384
D = 16384 * U / 10
10
16384
4000
Nominal range
5
8192
2000
0
0
0000
Not possible, is limited to 0 V
Underflow