EtherCAT Kommunikation

Transmitting process data

Access to I/O area

10

l

483

EDSIO1000 EN 7.0

10.2.1

Access to I/O area

SDO access can be used for read−only access to the object directory’s input and output data.

Input data

When accessing the input area of an I/O compound module, addressing takes place via
index 0x6000 + EtherCAT slot no. Subindexes give you access to the corresponding input
data. The relevant module description contains the subindex assignment.

Index

Subindex

Name

Type

Attr.

Default

Meaning

0x6000
...
0x603F

0x00

Input data

Unsigned8

ro

Number of input data
subindexes for the
corresponding EtherCAT
slot no.

0x01
0x02
...

ro
ro

Input data (see module
description)

Output data

During read−only access to the output area of an I/O compound module, addressing takes
place via index 0x7000 + EtherCAT slot no. Subindexes give you read−only access to the
corresponding output data. The relevant module description contains the subindex
assignment.

Index

Subindex

Name

Type

Attr.

Default

Meaning

0x7000
...
0x703F

0x00

Output data Unsigned8

ro

Number of output data
subindexes for the
corresponding EtherCAT
slot no.

0x01
0x02
...

ro
ro

Output data (see module
description)