Profinet communication – Lenze I/O system 1000 System Manual User Manual

Page 704

background image

PROFINET communication

Parameterising technology modules
RS232 interface − EPM−S640

12

l

704

EDSIO1000 EN 7.0

Parameter data 3964(R) protocol

Lenze

Description/value

Name

Data set

Lenze

Description/value

Name

Byte

No.

5

Acknowledgement time

The acknowledgement time defines the max.
permissible interval until the partner is acknowledged
while establishing/terminating a connection.
0 ... 65535 [20−ms steps] (00

h

.:. FF

h

)

0A

h

6

Block wait time

Maximum time between the recognition of a
requested frame (DLE) and the response.
0 ... 255 [ms] (00

h

... FF

h

)

0A

h

7

STX repetitions

Maximum number of times the module attempts to
establish a connection.
0 ... 255 [ms] (00

h

... FF

h

)

05

h

8

DBL

If the block wait time has been exceeded, the number
of STX repetitions for the requested protocol can be
specified here.
0 ... 255 [ms] (00

h

... FF

h

)

06

h

9

Priority

A communication partner has high priority if the
transmission attempt has priority over the partner’s
request to transmit. With a low priority, the partner’s
request to transmit comes first. In case of the protocols
3964(R), both partners must have different priorities.
00

h

: LOW

01

h

: HIGH

00