Product description

I/O compound modules − temperature measurement
Two analog inputs for thermocouple measurement − EPM−S405

3

l

154

EDSIO1000 EN 7.0

Terminals

Module terminals, spring terminals

1

View

Designation

Explanation

Terminal data

2

6

3

7

4

8

1

5

1

5

4

8

1

Analog input AI1 (+)

10 mm

0.08 ... 1.5 mm²

(AWG 28 ... 16)

2

Analog input AI1 (GND)

3

Not assigned

4

5

Analog input AI2 (+)

6

Analog input AI2 (GND)

7

Not assigned

SLIO002

8

)

Note!

ƒ

Use parameter setting to deactivate unused inputs.

ƒ

The module does not provide any auxiliary supply for sensors.

Technical data

EPM−S405: Rated data

Module identifier

1027

dec

Current consumption/power loss

Current consumption from backplane bus

75 mA

Power loss

1 W

Analog inputs

Number of inputs

2

Cable length

shielded

200 m

Load voltage

Nominal value

DC 24 V

Current consumption from load voltage
L+

30 mA (without load)

Voltage inputs

Input voltage ranges

−80 mV ... +80 mV

Destruction limit (input voltage)

30 V

Operational error limit

With interference frequency suppression:

± 0.1 %

Without interference frequency suppression:

± 0.3 %

Basic error limit

With interference frequency suppression:

± 0.05 %

Without interference frequency suppression:

± 0.25 %