Product description
I/O compound modules − temperature measurement
Two analog inputs for thermocouple measurement − EPM−S405
l
154
EDSIO1000 EN 7.0
Terminals
Module terminals, spring terminals
1
View
Designation
Explanation
Terminal data
2
6
3
7
4
8
1
5
1
5
4
8
1
Analog input AI1 (+)
10 mm
0.08 ... 1.5 mm²
(AWG 28 ... 16)
2
Analog input AI1 (GND)
3
Not assigned
4
5
Analog input AI2 (+)
6
Analog input AI2 (GND)
7
Not assigned
SLIO002
8
)
Note!
ƒ
Use parameter setting to deactivate unused inputs.
ƒ
The module does not provide any auxiliary supply for sensors.
Technical data
EPM−S405: Rated data
Module identifier
1027
dec
Current consumption/power loss
Current consumption from backplane bus
75 mA
Power loss
1 W
Analog inputs
Number of inputs
2
Cable length
shielded
200 m
Load voltage
Nominal value
DC 24 V
Current consumption from load voltage
L+
30 mA (without load)
Voltage inputs
Input voltage ranges
−80 mV ... +80 mV
Destruction limit (input voltage)
30 V
Operational error limit
With interference frequency suppression:
± 0.1 %
Without interference frequency suppression:
± 0.3 %
Basic error limit
With interference frequency suppression:
± 0.05 %
Without interference frequency suppression:
± 0.25 %