PROFINET communication

Parameterising technology modules

RS485 interface − EPM−S650

12

l

709

EDSIO1000 EN 7.0

Parameter data STX/ETX protocol

Lenze

Description/value

Name

Data set

Lenze

Description/value

Name

Byte

No.

9

End identifier 1

ASCII value of the end character that is sent after
a frame and marks the end of a transmission.
1 ... 255 (01

h

... FF

h

)

03

h

10

End identifier 2

ASCII value of the end character that is sent after
a frame and marks the end of a transmission.
1 ... 255 (01

h

... FF

h

)

00

h

11

Operating mode

Operating mode of the interface
00

h

: Half duplex − two−wire operation (RS485);

the data are transferred alternately in both
directions between the communication partners.
01

h

: Full duplex − four−wire operation (RS422);

the data are exchanged simultaneously between
the communication partners; transmission and
reception can take place at the same time. Each
communication partner must simultaneously
actuate a receive path.
Note: For the "Half duplex" parameterisation
under RS485, no software data flow control is
possible.

01

h

12

Cable assignment

For a connection with minimum reflections and
the open circuit detection in RS422/485
operation, the cables can be pre−assigned via
parameters with a defined idle level (

^ 228).

00

h

: No pre−assignment of the receive path. This

setting is only advisable for special drivers that
are provided with a bus capability.
01

h

: Signal R(A) 5 V (open circuit monitoring);

signal R(B) 0 V. In full duplex operation under
RS422, open circuit monitoring is possible.
02

h

: Signal R(A) 0 V; signal R(B) 5 V. This

pre−assignment corresponds to the idle state (no
transmitter active) in half duplex operation
under RS485. Open circuit monitoring is not
possible.

01

h