Product description – Lenze I/O system 1000 System Manual User Manual
Page 100
Product description
I/O compound modules − digital I/O
Four digital outputs 2 A − EPM−S309
l
100
EDSIO1000 EN 7.0
EPM−S309: rated data
Digital outputs
Number of outputs
4
Cable length
shielded
1000 m
unshielded
600 m
Load voltage
Nominal value
DC 24 (DC 20.4 ... 28.8 V)
Current consumption from load voltage
L+
20 mA (without load)
Total current
for each group, horizontal structure,
40°C
4 A
for each group, horizontal structure,
60°C
4 A
for each group, vertical structure
4 A
Output current
for "1" signal, nominal value
2 A
Output delay
from "0" to "1"
100
ms
from "1" to "0"
250
ms
Lamp load
10 W
Parallel switching of outputs
for redundant control
Not possible
for power increase
Not possible
Control of a digital input
Not possible
Switching frequencies
for ohmic loads
Max. 1000 Hz
for inductive loads
Max. 0.5 Hz
for lamp loads
Max. 10 Hz
Limitation (internal) of the inductive
breaking voltage
L+ (−52 V)
Short circuit protection of the output
Electronically
Operating threshold of the protection
system
2.7 A
Output data size
8 bits (with EPM−S110: 4 bits)
Status, alarm, diagnostics
Status display
Green LEDs per channel
Alarms
No
Process alarm
No
Diagnostic alarm
No
Diagnostic function
No
Diagnostic information can be read out
None
Module status
Green LED
Module error display
Red SF−LED
Channel error display
None
Electrical isolation
Between the channels and the backplane
bus
Yes
Insulation checked with
DC 500 V