6 electrical installation, 1 wiring according to emc, Electrical installation – Lenze I/O system 1000 System Manual User Manual

Page 245: Wiring according to emc, 6electrical installation

background image

Electrical installation

Wiring according to EMC

6

l

245

EDSIO1000 EN 7.0

6

Electrical installation

6.1

Wiring according to EMC

General notes

l

The electromagnetic compatibility of the system depends on the type of installation and care
taken. Especially consider the following:
– Assembly
– Shielding
– Earthing

l

For installations differing from the one described, the evaluation of the conformity with the
EMC Directive requires a check of the system regarding the EMC limit values. This for instance
applies to:
– Use of unshielded cables

l

The compliance with the EMC Directive is in the responsibility of the user.
– If you observe the following measures, you can assume that no EMC problems will occur

during operation and that compliance with the EMC Directive and the EMC law is achieved.

– If devices which do not comply with the CE requirement concerning noise immunity (EN

6100042) are operated close to the system, these devices may be electromagnetically
affected by the system.

Assembly

l

Provide electrical contact between the DIN rail and the earthed mounting plate:
– Mounting plates with electrically conductive surfaces (zinc−coated or stainless steel) allow

permanent contact.

– Painted plates are not suitable for an EMC−compliant installation.

l

If you use several mounting plates:
– Connect as much surface of the mounting plates as possible (e.g. with copper strips).

l

When laying the cables, pay attention to the separation of signal cables and mains cables.

l

Lay the cables as close as possible to the reference potential. Freely suspended cables act like
aerials.

Shielding

l

Only use cables with braided shield if possible.

l

The overlap rate of the shield should be higher than 80%.

l

For data cables for serial connection, always use metal or metallised connectors. Connect the
shield of the data cable to the connector shell.

Earthing

l

Earth all metallically conductive components using suitable cables connected to a central
earthing point (PE bar).

l

Keep to the minimum cross−sections defined in the safety instructions:
– For EMC not the cable cross−section is important, but the surface of the cable and the

contact with a cross−section as large as possible, i.e. large surface.