beautypg.com

Product description, Technical data – Lenze I/O system 1000 System Manual User Manual

Page 78

background image

Product description

I/O compound modules − digital I/O
Four digital inputs (three−wire conductor connection) − EPM−S203

3

l

78

EDSIO1000 EN 7.0

Technical data

EPM−S203: Rated data

Module identifier

8

dec

Current consumption/power loss

Current consumption from backplane bus

55 mA

Power loss

0.6 W

Digital inputs

Number of inputs

4

Cable length

shielded

1000 m

unshielded

600 m

Input voltage

Nominal value

DC 24 (DC 20.4 ... 28.8 V)

for signal "0"

DC 0 ... 5 V

for signal "1"

DC 15 ... 28.8 V

Input current

for signal "1"

3 mA

2−wire BERO

Connection possible

Yes

Max. permissible closed−circuit current

0.5 mA

Input delay

from "0" to "1"

3 ms

from "1" to "0"

3 ms

Number of inputs which can be used simultaneously

horizontal structure

4

vertical structure

4

Input characteristic

IEC 61131

Input data size

8 bits (with EPM−S110: 4 bits)

Status, alarm, diagnostics

Status display

Green LEDs per channel

Alarms

No

Process alarm

No

Diagnostic alarm

No

Diagnostic function

No

Diagnostic information can be read out

None

Module status

Green LED

Module error display

Red LED

Channel error display

None

Electrical isolation

Between channels and the backplane bus

Yes

Insulation checked with

DC 500 V