Product description

I/O compound modules − counter

One counter 32 bits, 24 V DC − EPM−S600

3

l

171

EDSIO1000 EN 7.0

B) Function mode in the case of comparison value with zero pulse duration

When the comparison condition is met, hysteresis becomes active. When hysteresis is
active, the comparison result remains unchanged until the count value exits the hysteresis
range set. After the hysteresis range is exited, hysteresis is only activated again when the
comparison conditions are met.

8
7
6
5
4
3
2
1
0

Comparison

value

Hysteresis

Comparison bit:

Hysteresis = 0

Hysteresis = 3

Count value

1

2

3

4

5

6

7

SLIO042

 Count value = comparison value ®Output is set and hysteresis is activated

‚ Exiting of the hysteresis range ®Output is reset and count value < comparison value

ƒ Count value = comparison value ®Output is set and hysteresis is activated

„ Output is reset due to exiting of the hysteresis range and count value > comparison value

… Count value = comparison value ®Output is set and hysteresis is activated

† Count value = comparison value and hysteresis active ® Output remains set

‡ Exiting of the hysteresis range and count value > comparison value ® Output is reset