Modbus tcp kommunikation, Register assignment – Lenze I/O system 1000 System Manual User Manual
Page 723
![background image](/manuals/565636/723/background.png)
Modbus TCP Kommunikation
Access to the I/O system 1000
Access to diagnostic data
l
723
EDSIO1000 EN 7.0
Register assignment
Address
Access to
0x/1x:
4000
h
... 403F
h
Bit access to process alarm status:
0x/1x: 4000: Process alarm status Modbus TCP slot 0
0x/1x: 4001: Process alarm status Modbus TCP slot 1
...
0x/1x: 403F: Process alarm status Modbus TCP slot 63
0x/1x:
5000
h
... 503F
h
Bit access to diagnostic alarm status:
0x/1x: 5000: Diagnostic alarm status Modbus TCP slot 0
0x/1x: 5001: Diagnostic alarm status Modbus TCP slot 1
...
0x/1x: 503F: Diagnostic alarm status Modbus TCP slot 63
3x: 4000
h
... 41FF
h
Word access to process alarm data
3x: 4000
h
... 4007
h
: Modbus TCP slot 0
3x: 4008
h
... 400F
h
: Modbus TCP slot 1
...
3x: 41F8
h
... 41FF
h
: Modbus TCP slot 63
3x: 4000
h
... 4007
h
16 bytes of process alarm data of Modbus TCP slot 0
3x: 4008
h
... 400F
h
16 bytes of process alarm data of Modbus TCP slot 1
3x: 4010
h
... 4017
h
16 bytes of process alarm data of Modbus TCP slot 2
...
...
3x: 41F8
h
... 41FF
h
16 bytes of process alarm data of Modbus TCP slot 63
3x: 5000
h
... 500F
h
32 bytes of diagnostic alarm data of Modbus TCP slot 0
3x: 5010
h
... 501F
h
32 bytes of diagnostic alarm data of Modbus TCP slot 1
...
3x: 53F0
h
... 53FF
h
32 bytes of diagnostic alarm data of Modbus TCP slot 63