Modbus TCP Kommunikation

Access to the I/O system 1000

Access to diagnostic data

13

l

723

EDSIO1000 EN 7.0

Register assignment

Address

Access to

0x/1x:
4000

h

... 403F

h

Bit access to process alarm status:
0x/1x: 4000: Process alarm status Modbus TCP slot 0
0x/1x: 4001: Process alarm status Modbus TCP slot 1
...
0x/1x: 403F: Process alarm status Modbus TCP slot 63

0x/1x:
5000

h

... 503F

h

Bit access to diagnostic alarm status:
0x/1x: 5000: Diagnostic alarm status Modbus TCP slot 0
0x/1x: 5001: Diagnostic alarm status Modbus TCP slot 1
...
0x/1x: 503F: Diagnostic alarm status Modbus TCP slot 63

3x: 4000

h

... 41FF

h

Word access to process alarm data
3x: 4000

h

... 4007

h

: Modbus TCP slot 0

3x: 4008

h

... 400F

h

: Modbus TCP slot 1

...
3x: 41F8

h

... 41FF

h

: Modbus TCP slot 63

3x: 4000

h

... 4007

h

16 bytes of process alarm data of Modbus TCP slot 0

3x: 4008

h

... 400F

h

16 bytes of process alarm data of Modbus TCP slot 1

3x: 4010

h

... 4017

h

16 bytes of process alarm data of Modbus TCP slot 2

...

...

3x: 41F8

h

... 41FF

h

16 bytes of process alarm data of Modbus TCP slot 63

3x: 5000

h

... 500F

h

32 bytes of diagnostic alarm data of Modbus TCP slot 0

3x: 5010

h

... 501F

h

32 bytes of diagnostic alarm data of Modbus TCP slot 1

...

3x: 53F0

h

... 53FF

h

32 bytes of diagnostic alarm data of Modbus TCP slot 63