beautypg.com

Product description – Lenze I/O system 1000 System Manual User Manual

Page 209

background image

Product description

I/O compound modules − counter

Two counters 32 bits, 24 V DC − EPM−S603

3

l

209

EDSIO1000 EN 7.0

Counting continuously

Limits

Counting range

Lower counting limit

−2 147 483 648 (−2

31

)

Upper counting limit

+2 147 483 647 (2

31

−1)

Function:

ƒ

For starting the counting process the internal gate has to be opened.
– The counter always counts from 0.
– If the counter reaches the upper counting limit when counting forwards, and if a

further count pulse in positive direction occurs, the counter skips to the lower
counting limit and continues to count from there.

– If the counter reaches the lower counting limit when counting backwards, and if a

further negative count pulse occurs, the counter skips to the upper counting limit
and continues to count from there.

– If values are exceeded or not reached, the status bits STS_OFLW or STS_UFLW are

set. These bits remain set until they are reset with RES_SET in the control word.

ƒ

For stopping the counting process the internal gate has to be closed.

Upper counting

limit value

Lower counting

limit value

0

Counter starts

Counter starts

Counter stops

Counter stops

Overflow

Underflow

Time

Counter content

SLIO046

Fig. 3−69

Example of "Counting continuously"