CANopen communication

Parameterising technology modules

2 digital outputs with PWM functionality − EPM−S620

8

l

327

EDSIO1000 EN 7.0

8.13

Parameterising technology modules

8.13.1

2 digital outputs with PWM functionality − EPM−S620

Parameter data

Index/sub
index

Name

Description/value

Lenze

0x3100/x

PWM 1:
Period byte 3

Set parameters here for the total time for pulse
duration and pulse pause. The time should be selected
as a factor for the 20.83 ns basis.
Values below 25

ms are ignored. If the pulse duration is

higher or equal to the period, the DO output is set
permanently.
Value range: 1200 ... 8388607 (25

ms ... approx. 175 ms)

1F40

h

0x3101/x

PWM 1:
Period byte 2

0x3102/x

PWM 1:
Period byte 1

0x3103/x

PWM 1:
Period byte 0

0x3104/x

PWM 2:
Period byte 3

1F40

h

0x3105/x

PWM 2:
Period byte 2

0x3106/x

PWM 2:
Period byte 1

0x3107/x

PWM 2:
Period byte 0

0x3108/x
...
0x3129/x

Reserved

0x5620/x

PWM pulse duration

Selection of pulse duration
Permissible values. 48 ... 8388607 (corresponds to 1 ...
175000

ms

)

Note!

The pulse/pause ratio is determined by specifying the period (0x3100 ...
0x3107) and pulse duration (0x5620).