13 parameterising technology modules, Canopen communication – Lenze I/O system 1000 System Manual User Manual
Page 327
CANopen communication
Parameterising technology modules
2 digital outputs with PWM functionality − EPM−S620
l
327
EDSIO1000 EN 7.0
8.13
Parameterising technology modules
8.13.1
2 digital outputs with PWM functionality − EPM−S620
Parameter data
Index/sub
index
Name
Description/value
Lenze
0x3100/x
PWM 1:
Period byte 3
Set parameters here for the total time for pulse
duration and pulse pause. The time should be selected
as a factor for the 20.83 ns basis.
Values below 25
ms are ignored. If the pulse duration is
higher or equal to the period, the DO output is set
permanently.
Value range: 1200 ... 8388607 (25
ms ... approx. 175 ms)
1F40
h
0x3101/x
PWM 1:
Period byte 2
0x3102/x
PWM 1:
Period byte 1
0x3103/x
PWM 1:
Period byte 0
0x3104/x
PWM 2:
Period byte 3
1F40
h
0x3105/x
PWM 2:
Period byte 2
0x3106/x
PWM 2:
Period byte 1
0x3107/x
PWM 2:
Period byte 0
0x3108/x
...
0x3129/x
Reserved
0x5620/x
PWM pulse duration
Selection of pulse duration
Permissible values. 48 ... 8388607 (corresponds to 1 ...
175000
ms
)
Note!
The pulse/pause ratio is determined by specifying the period (0x3100 ...
0x3107) and pulse duration (0x5620).