Product description – Lenze I/O system 1000 System Manual User Manual
Page 123
![background image](/manuals/565636/123/background.png)
Product description
I/O compound modules − analog I/O
4 analog inputs 0/4 ... 20 mA (12 bits) − EPM−S403
l
123
EDSIO1000 EN 7.0
Technical data
EPM−S403: Rated data
Module identifier
1029
dec
Current consumption/power loss
Current consumption from backplane bus
70 mA
Power loss
0.7 W
Analog inputs
Number of inputs
4
Cable length
shielded
200 m
Load voltage
Nominal value
DC 24 V
Current consumpt. from load voltage L+
15 mA (without load)
Current inputs
Input current ranges
0 mA ... +20 mA
+4 mA ... +20 mA
Destruction limit (input current)
40 mA
Max. input resistance
110
W
Operational error limit
+/− 0.3 % ... +/− 0.5 %
Basic error limit
+/− 0.2 % ... +/− 0.3 %
Measuring principle
Gradual approximation
Resolution
12 bits
Basic conversion time
4 ms all channels
Interference voltage suppression for a
frequency of
> 50 dB at 50 Hz (UCM < 2 V)
Temperature error
(relating to input range)
± 0.005 %/K
Linearity distortion
(relating to input range)
± 0.02 %
Repeat accuracy (in steady−state vibration at
25°C, relating to the input range)
± 0.05 %
Input data size
8 bytes
Status, alarm, diagnostics
Status display
Yes
Alarms
No
Process alarm
No
Diagnostic alarm
No
Diagnostic function
Yes
Diagnostic information can be read out
Possible
Module status
Green LED
Module error display
Red LED
Channel error display
Red LEDs per channel