beautypg.com

Product description, Technical data – Lenze I/O system 1000 System Manual User Manual

Page 150

background image

Product description

I/O compound modules − temperature measurement
Four (two) analog inputs for resistance tests − EPM−S404

3

l

150

EDSIO1000 EN 7.0

Technical data

EPM−S404: Rated data

Module identifier

1030

dec

Current consumption/power loss

Current consumption from backplane bus

75 mA

Power loss

1 W

Analog inputs

Number of inputs

4

Cable length

shielded

200 m

Load voltage

Nominal value

DC 24 V

Current consumption from load voltage
L+

30 mA (without load)

Resistor inputs

Resistance ranges

0 ... 60

W

0 ... 600

W

0 ... 3000

W

Operational error limit

± 0.4 %

Basic error limit

± 0.2 %

Resistance thermometer inputs

Resistance thermometer ranges

Pt100
Pt1000
Ni100
Ni1000

Operational error limit

± 0.4 %

Basic error limit

± 0.2 %

Measuring principle

Sigma−delta

Resolution

16 bits

Basic conversion time

4.2 ... 324.1 ms (50 Hz) per channel
3.8 ... 270.5 ms (60 Hz) per channel

Interference voltage suppression for a
frequency of

> 80 dB at 50 Hz (UCM < 60 V)

Destruction limit (input voltage)

9 V

Temperature error
(relating to input range)

± 0.005 %/K

Linearity distortion
(relating to input range)

± 0.005 %

Repeat accuracy (in steady−state vibration at
25°C, relating to the input range)

± 0.05 %

Input data size

8 bytes

Status, alarm, diagnostics

Status display

Yes

Alarms

Yes, parameterisable

Process alarm

Yes, parameterisable

Diagnostic alarm

Yes, parameterisable

Diagnostic function

Yes

Diagnostic information can be read out

Possible

Module status

Green LED

Module error display

Red LED

Channel error display

Red LEDs per channel