beautypg.com

Devicenet communication – Lenze I/O system 1000 System Manual User Manual

Page 593

background image

DeviceNet communication

Parameterising the counter

One counter 32 bits, 5 V DC − EPM−S602

11

l

593

EDSIO1000 EN 7.0

Lenze

Description/value

Name

Pos. in
string of
digits

9

Signal evaluation

Bits 2 ... 0: Signal evaluation

000

b

= counter deactivated (the other parameter details for

the counter are ignored)
001

b

= rotary transducer single (at A and B)

010

b

= rotary transducer double (at A and B)

011

b

= rotary transducer quadruple (at A and B)

100

b

= direction (pulse at A and direction at B)

Bits 6 ... 3: Reserved
Bit 7: Gate function (internal gate)

0= abort (counting process starts again from loading value)
1 = interrupt (counting process is continued with counter
content)

00

h

10

Final value

Counting method:
0x310D: byte 3 (high byte)
0x310E: byte 2
0x311F: byte 1
0x3110: byte 0 (low byte)

00

h

11

Loading value

Counting method:
0x3109: byte 3 (high byte)
0x310A: byte 2
0x310B: byte 1
0x310C: byte 0 (low byte)

00

h

12

Hysteresis

00

h