20 index table, Canopen communication, Index table – Lenze I/O system 1000 System Manual User Manual
Page 360: How to read the index table
![background image](/manuals/565636/360/background.png)
CANopen communication
Index table
l
360
EDSIO1000 EN 7.0
8.20
Index table
ƒ
The indices are numbered in ascending order for reference purposes.
ƒ
How to read the index table:
Column
Abbreviation
Meaning
Index
Ixxxx
h
Index Ixxxx
h
1
Subindex 1 of Ixxxx
h
2
Subindex 2 of Ixxxx
h
Ixxxx
h
¿
After entry, the index parameter value is stored in the EEPROM
Ixxxx
h
*
Index parameter value is stored in the EEPROM with I2003
h
= 1
Name
Index name
Lenze
Lenze setting, setting on delivery
Selection
1
{%}
99 Min. value (unit) max. value
Important
–
Brief, important explanations
^ Page x
Reference to detailed explanations
Index
Name
Possible settings
Important
Lenze Selection
I1000
h
Device type
Display only
Type
I1001
h
Error register
Display only
^ 349
Bit 0
Generic
An unspecified error has
occurred (flag set on each
error message)
Bit 1
Reserved
Bit2
Reserved
Bit3
Reserved
Bit4
Comm.
Communication error
(Overrun CAN)
Bit 5
Reserved
Bit6
Reserved
Bit 7
ManSpe
c.
Manufacturer−specific error
Shown in detail in I1003
h
I1003
h
Display only
Fault memory
1 Actual errors
I1004
h
Number of
supported
PDOs
Display only
1 Number of
synchronous
PDOs
supported
2 Number of
synchronous
PDOs
supported
I1005
h
*
Sync COB−ID
128
128
{1}
2047