PROFIBUS communication

Parameterising the counter

Two counters 32 bits, 24 V DC − EPM−S603

9

l

453

EDSIO1000 EN 7.0

Diagnostic data

Using the SFB 52 you can access the diagnostic data of the module anytime. Since this
module does not support a process alarm, the diagnostic data serve to provide information
on this module.

Data set 1 is structured as follows:

Byte

Bit 7 ... 0

0

0 (fixed)

1

Bit 3 ... 0: Module class, 1000

b

: function module

Bit 4: Channel information available
Bit 7 ... 5: 0 (fixed)

2

0 (fixed)

3

0 (fixed)

4

Bit 6 ... 0: Channel type, 76h: counter module
Bit 7: Further channel types available, 0: no, 1: yes

5

Number of diagnostic bits output by the module per channel (here 00

h

)

6

Number of channels of a module (here 02

h

)

7 ... 15

0 (fixed)